3Phase Online UPS

3 PHASE Industrial Online UPS

Advanced DSP Technology

Remote Monitoring loT

3 Phase Star/Delta

IGBT Based Design

It's all in the details

6 Stage Battery Charging

Configurable User Settings

Multiple Battery Selection

some text 

some text 

some text 

some text 

How it works?

3 PHASE Industrial Online UPS

Available Models

Technical Specification

Models/Ratings

RATINGS 5KVA7.5KVA 10KVA15KVA 20KVA 25KVA 30KVA 40KVA 50KVA60KVA80KVA100KVA120KVA150KVA
OPERATING DC VOLTAGE 240V/360V240V/360V 240V/360V240V/360V 240V/360V 360V 360V 420V 420V420V480V480V480V480V
OVERLOAD AMPS5.7Amps8.6Amps11.5Amps17.3Amps23.1Amps28.9Amps34.7Amps46.3Amps57.9Amps69.5Amps92.7Amps115.9Amps139.1Amps173.9Amps
OVERLOAD WATTAGE 4KW6KW8KW12KW16KW20KW24KW32KW40KW48KW64KW80KW96KW120KW


3-PHASE ONLINE UPS WITH MPPT CHARGE CONTROLLER


MPPT Based Charge Controller


Switching Element

IGBT Module


Controller

DSP


Efficiency

>95%


Max Current From Solar

60Amps


Battery Charging Stages

5(Softstart, Boost, Absorbtion, Float, Equalise)


Battery


Low Cut Off

10.5V/Battery +/- 2%


Low Cut Off Recovery

11.5V/Battery +/- 2%


Low Buzzer

10.7/Battery +/-2%


High Cut Off

15.5/Battery +/-2%


High Cut Off Recovery

15.0/Battery +/-2%


Boost Charging Volt by SPV

14.5/Battery +/-2%


Boost Charging Volt by Grid

14.0/Battery +/-2%


Charging Current by Grid

10A +/-2%


No Load Battery Current

0.02%


Output


Output@ No Load

415 V AC +/-2%


Output Frequency

50+/-2%


Output Capacity

100% - 120% : 60 Seconds with 3 Times Auto Reset, 

120%-150% : 5 Seconds,>150%: 1 Second


Output Low Retry

1 Time


Output Short Circuit

1 Time


Grid


No of Phase

380V-480V 3 PHASE 4 WIRE(R,Y,B,N)


Frequency Range

45-55 Hz+/-10%


Power Factor

0.95


Charger Topology

Buck/Buck-Boost


Display


Display

20X4 LCD


Parameters

OUTPUT- Voltage(R,Y,B), Current(R,Y,B), and Frequency(R,Y,B)

INPUT(Grid)- Voltage(R,Y,B), and Frequency(R,Y,B)

SOLAR- Voltage, Current, Power and Energy (Optional)

BATTERY- Voltage, Current, Level(Bar Graph)

STATUS/FAULTS- Inverter Status, Mains Status, Charger Status, and Battery Status/Charging Stages


Inverter


Switching Element

IGBT Module


Output Waveform

Digitally Filtered Pure Sine Wave


Changeover (Mains to Inverter)

0 ms


Output Power Factor

0.8


Overload Retry

3 Times


Indication(LED)

Inverter On, Mains In Range, Battery Low/High, Charger On, Overload, Faults


Alarm(Audible)

Battery Low, Overload, Charger On, Inverter, Solar Charger On


Protection

Overload, Short Circuit Protection, Over Voltage, SPV Surge and Transient protection (MOV Varistors), Reverse Polarity of Battery, Over temperature Protection, Under Voltage and Over Voltage and Over Voltage Protection 


Cooling

Forced Air cooling (Temp controlled)


Communication

Remote Monitoring System (Over GPRS/BLE and Wifi) or RS232


Operating Temp

0-50C


Operating Humidity

95%


Protection class

IP20

 

NOTE: Due to continuous improvement in the product and design. These specification may deviate a bit from the actual product, but only in a better way. 